                          There are a lot of parameters which effects to the cooling 
                          tower design and operation. Some will be discussed here 
                          through the examples below. 
                        Example 4-1. 
                          The water circulating rate is one of most important 
                          primary variables. Obviously it is a key number in the 
                          original design. A problem frequently encountered is 
                          the prediction of the effects of changes in water circulation 
                          rate on the temperatures of the water entering and leaving 
                          an existing cooling tower. Assume an existing mechanical 
                          draft cooling tower is operating at the following conditions, 
                          and estimate the cold & hot water temperature when 
                          the water flow rate is increased to 20,000 GPM, assuming 
                          no change in the entering air mass flow rate, wet bulb 
                          temperature, and heat load. (Actually, the air mass 
                          is decreased due to the increase of pressure drop at 
                          the fill with the increase of water.) 
                         Given, 
                         
                          - Water Flow Rate (L1): 
                            16000
 
                          - Entering Air Flow Rate 
                            (G1): 80848
 
                          - Ambient Wet Bulb Temperature: 
                            80.0
 
                          - Site Altitude: sea level
 
                          - Hot Water Temperature 
                            (HWT, tw2): 104.0
 
                          - Cold Water Temperature 
                            (CWT, tw1): 89.0
 
                          - Characteristic Curve Slope 
                            (m): -0.800
 
                          - Alternative Water Flow 
                            Rate (L2): 20000
 
                         
                        (Solution) 
                          Range, R1 = HWT - CWT = tw2 - 
                          tw1 = 104 - 89 = 15oF 
                          Water Flow Rate in Pound, L1 = Water Flow 
                          Rate x (500 / 60) = 16,000 x (500 / 60) = 133,333.3 
                          lb/min 
                          Heat Load, D1 = L1 x R1 
                          = 133,333.3 x 15 = 2,000,000 BTU/min 
                          Air Mass Flow Rate, G1 = 80,848 lb/min 
                          Liquid to Gas Ratio, L/G1 = L1 
                          / G1 = 133,333.3 / 80,848 = 1.6492 
                          Water Flow Rate in Pound, L2 = Water Flow 
                          Rate x (500 / 60) = 20,000 x (500 / 60) = 166,666.7 
                          lb/min 
                          Heat Load, D2 = D1 = 2,000,000 
                          BTU/min 
                          Air Mass Flow Rate, G2 = G1 = 
                          80,848 lb/min 
                          Liquid to Gas Ratio, L/G2 = L2 
                          / G2 = 166,666.7 / 80,848 = 2.0615 
                          Range, R2 = D2 / L2 
                          = 2,000,000 / 166,666.7 or = R1 x (L1 
                          / L2) = 12oF 
                          (The range must be calculated since the heat load is 
                          same as the design condition but water flow rate was 
                          changed.) 
                        In estimating the cold water 
                          temperature with the new water flow rate, there are 
                          two methods. One is to find a new approach by means 
                          of the computer. Another is to find it using the CTI 
                          performance curves. Two methods shall be discussed. 
                          With the use of the computer, the iteration is required 
                          until the value of the new tower characteristic is exactly 
                          equal to the new KaV/L (NTU) varying the approach by 
                          means of computer. 
                        First Step: Calculate 
                          NTU at the design conditions as follows; 
                        
                           
                            |  
                               WATER SIDE  | 
                             
                               AIR SIDE  | 
                              ENTH 
                                DIFF.  | 
                           
                           
                            |   Descriptions  | 
                              tw 
                                (oF)  | 
                              hw 
                                (Btu/Lb)  | 
                              Description  | 
                              ha 
                                (Btu/Lb)  | 
                              1/(hw-ha)  | 
                           
                           
                            |   tw1 
                                + 0.1 x R  | 
                              90.50  | 
                              56.6478  | 
                              ha1 
                                + 0.1 x L/G x R  | 
                              46.1645  | 
                              0.0954  | 
                           
                           
                            |   tw1 
                                + 0.4 x R  | 
                              95.00  | 
                              63.3426  | 
                              ha1 
                                + 0.4 x L/G x R  | 
                              53.5858  | 
                              0.1025  | 
                           
                           
                            |   tw1 
                                + 0.6 x R  | 
                              98.00  | 
                              68.2591  | 
                              ha1 
                                + 0.6 x L/G x R  | 
                              58.5334  | 
                              0.1028  | 
                           
                           
                            |   tw1 
                                + 0.9 x R  | 
                              102.50  | 
                              76.4013  | 
                              ha1 
                                + 0.9 x L/G x R  | 
                              65.9547  | 
                              0.0957  | 
                           
                           
                            |  
                               Sum 
                                of 1 / (hw - ha)   | 
                              0.3964  | 
                           
                           
                            |  
                               Total Tower Demand 
                                (NTU) = Cooling Range x Sum of 1 / (hw - ha)   | 
                              1.4866  | 
                           
                         
                        Second Step: Calculate 
                          a value of "C" of tower characteristic for 
                          the design conditions as follows; 
                        C = KaV/L / (L/G1)-m 
                          = KaV/L x (L/G1)m = 1.4866 x (1.6492)0.8 
                          = 2.21825 
                        Third Step: Calculate 
                          a new tower characteristic for the increased water flow 
                          as follows; 
                        New Tower Characteristic 
                          = C x (L/G2)-m = 2.21825 x (2.0615)- 
                          0.8 = 1.2436 
                          (Note that "C" value is a constant value regardless 
                          the change of water flow rate in finding the approach 
                          at the alternative temperature conditions.) The new 
                          tower characteristic for the increased water flow rate 
                          can be calculated as above. 
                        Forth Step: Iterate 
                          until the value of new characteristic is equal to the 
                          new NTU varying the value of approach. 
                         To be continued. Please press the next button....  |