|    
                           
                          (5) Fan Starting Requirements: Fan equipment inertia 
                          must be overcome in order to bring the fan up to speed. 
                          The time taken to accelerate the fan to full speed must 
                          be within the motor winding limitations or the life 
                          of the motor will be reduced. It is important to know 
                          the inertia moment for fan, gear reducer and coupling 
                          shaft, the speed torque curve for fan including the 
                          efficiency of fan system and gear reducer, the motor 
                          capability (acceleration torque = pull up torque), and 
                          allowable starting time for the motor and the starter. 
                        The inertia of an driver 
                          indicates the energy required to keep the system running. 
                          However, starting or accelerating the system requires 
                          extra energy. The torque required to accelerate a body 
                          is equal to the WR2 of the body, times the 
                          change in rpm, divided by 308 times the interval (in 
                          second) in which this acceleration takes places: 
                        Accelerating Torque, Tacc 
                          = WR2 x N / (308 x t) (lb-ft) 
                        Where, 
                          N: Change in rpm 
                          W: Weight in lbs 
                          R: Radius of Gyration 
                          t: Time of Acceleration in seconds 
                          WR2: Inertia Moment 
                          308: This constant is derived by transferring linear 
                          motion to angular motion, and considering acceleration 
                          due to gravity. 
                        The fan is reached to the 
                          full speed of fan in 3-5 seconds. This means that it 
                          takes 3-5 seconds motor to reach the full speed of motor. 
                          The time that it takes to accelerate an induction motor 
                          from zero to full speed may be found from the following 
                          equation. 
                        Motor Starting Time 
                          = (WRm2 + WRs2 
                          + WRg2 + WRf2) 
                          x N / (308 x Tacc) (second) 
                        Where, 
                          WR2: Moment of Inertia 
                          WRm2: Inertia of Motor (lb-ft2) 
                          WRs2: Inertia of Shaft (lb-ft2) 
                          WRg2: Inertia of Gearbox (lb-ft2) 
                          at the speed of motor 
                          WRf2: Inertia of Fan (lb-ft2) 
                          at the speed of motor 
                          Tacc (Average Accelerating Torque) = 0.8 
                          x {(Ts + Tm)} / 2 - TL 
                          = Pull Up Torque 
                          Ts: Starting Torque 
                          Tm: Maximum Torque (= Breakdown Torque) 
                          TL: Full Load Torque 
                          N: Motor Speed 
                        Since the moment of inertia 
                          of fan is in reference to the fan shaft speed, it should 
                          be converted to the motor speed by the following relationship: 
                        WRf2 
                          at motor speed = WRf2 at fan speed 
                          x (1/Gear Ratio)2 
                        In order to find the total 
                          time required to accelerate the motor and mechanical 
                          equipment of cooling tower, the area between the motor 
                          speed-torque curve and the fan speed-torque curve which 
                          is including the efficiencies of gear reducer and cooling 
                          tower system, is divided into strips, the ends of which 
                          approximate straight lines. Each strip corresponds to 
                          a speed increment which takes place within a definite 
                          time interval. 
                        Let's calculate the acceleration 
                          torque and horsepower about below sample. 
                        
                          - WR2 of Motor: 
                            64.3 lb-ft2 (1,770 RPM, 3 seconds of acceleration 
                            time)
 
                          - WR2 of Shaft: 
                            2.4 lb-ft2
 
                          - WR2 of Gear 
                            Reducer: 4.350 lb-ft2at high speed shaft 
                            (or 852.60 lb-ft2 at low speed shaft)
 
                          - WR2 of Fan: 
                            34,260 lb-ft2
 
                          - Gear Reduction Ratio: 
                            14.0:1
 
                         
                        Then, Equivalent WR2= 
                          64.3 + 2.4 + 852.6 (1/14.0)2 + 34,260 (1/14.0) 
                          2 = 245.85 lb-ft2 
                        Now, accelerating torque 
                          can be determined: 
                        Tacc = (Equivalent 
                          WR2 x N) / (308 x t) 
                          = (245.85 x 1,770) / (308 x 3) 
                          = 470.94 lb-ft 
                          (Note that the engineers always have to check the acceleration 
                          torque of motor for maintaining the starting time required 
                          and the motor life service.) 
                        Now, horsepower to accelerate 
                          is: 
                        HPacc = (Tacc 
                          x N) / 5250 
                          = 470.94 x 1,770 / 5250 
                          = 158.77 hp 
                        From this, the size of the 
                          motor which will accelerate and run the load can be 
                          determined. Losses must be considered here. Throughout 
                          these example, we have assumed no losses due to friction, 
                          heat, etc. Obviously, there are friction losses, and 
                          if, say 10% of power is lost, it at be made up. 
                        HPLosses = (10%) 
                          x (HPacc) 
                          = 10% x 158.77 = 15.88 
                        Therefore, total horsepower 
                          is: 
                        HPTotal = HPacc 
                          + HPLosses 
                          = 158.77 + 15.88 = 174.65 or approximately 175 HP 
                        Thus, it takes 175 horsepower 
                          to accelerate and run this system. 
                        4) Motor Input Power Rating 
                        The horse power shown on 
                          the fan rating sheet is the net shaft break horsepower 
                          that the fan requires. Thus, the necessary input motor 
                          power must be calculated referring factors below. 
                        
                          - Motor efficiency
 
                          - Gear reducer drive efficiency
 
                          - System efficiency
 
                         
                        Motor efficiencies are obtained 
                          from motor manufacturers and usually range from 0.85 
                          to 0.96. Gear reducer drive efficiencies range typically 
                          0.92 to 0.97. System efficiencies are more difficult 
                          to assess. As you see the footnote of fan rating sheet, 
                          Hudson fans are tested in nearly perfect conditions 
                          of very close tip clearance, good inlet conditions and 
                          minimal obstructions from beams. It is likely the actual 
                          tower system will not be as ideal as Hudson's performance 
                          curve conditions. Unless you have compared your system 
                          to Hudson's one by means of wind tunnel or other method, 
                          we suggest using a system efficiency of 0.95. 
                        Since actual operating conditions 
                          of commercial equipment will vary from wind tunnel test 
                          conditions, proper environmental correction factors 
                          must be applied to both total pressure and horsepower. 
                          These environmental factors include inlet and exit air 
                          flow conditions, tip clearance, obstructions to air 
                          flow, plenum geometry, etc. Therefore actual fan efficiencies 
                          will be different from those indicated unless the actual 
                          environmental system is equivalent to the test conditions. 
                         Input Horsepower = BHP 
                          / (Effm x Effg x Effs) 
                        Where, 
                          Effm: Motor efficiency 
                          Effg: Gear reducer efficiency 
                          Effs: System efficiency 
                        Air horsepower which is the 
                          actual output of the fan is calculated by: 
                        HPAir = Total 
                          Pressure x CFM / (6356 x Efficiency) 
                        5) Motor Output Power Rating 
                        
                          - Power required = Fan BHP 
                            / (Efficiencies of Fan System and Gear Reducer)
 
                          - Minimum Power to be installed 
                            = Power required x 1.10 of Design Margin
 
                         
                        In case of previous sample 
                          job, 
                        Power required = 139.8 hp 
                          / (0.95 of fan system efficiency x 0.95 of gear reducer 
                          efficiency) 
                          = 154.90 hp 
                        Minimum Power to be installed 
                          = 154.90 x 1.1 of design margin 
                          = 170.39 hp 
                        Therefore, the next available 
                          size of motor power is 175 hp. 
                        6) Consequent Pole Speed 
                          Controls 
                        This is limited to the case 
                          of using the polypole change motor. Pole changing is 
                          handled by switching circuits that resemble some of 
                          those controls. The choice of which motor type to use 
                          depends on the speed versus torque requirements of the 
                          driven load. In the application of the cooling tower 
                          axial fan, the type of load is a variable torque, since 
                          the fan power required at the low speed is reduced to 
                          a cubic speed ratio (= low speed/high speed). The actual 
                          circuit used will require a three-terminal contactor 
                          for one speed and a five-terminal contactor for the 
                          other. There are three classes of consequent pole motors 
                          depending on their intended service. The NEMA has standardized 
                          the terms as follows: 
                        
                          - Constant Torque Motor: 
                            This control is to obtain the same rated torque at 
                            both high and low speed. These motors are connected 
                            in parallel wye for high speed and series delta for 
                            low speed.
 
                          - Constant Horsepower Motor: 
                            This control is to obtain the same rated power at 
                            both high and low speed. These motors are connected 
                            in-series delta for high speed and parallel wye for 
                            low speed.
 
                          - Variable Torque Motor: 
                            This is to obtain the rated torque directly proportional 
                            to speed at either high or low speed. These motors 
                            are connected in parallel wye for high speed and series 
                            wye for low speed.
 
                              
                          |