3) Chemical Treatment for Corrosion, Scale and Deposit
Control
Many different
kinds of chemical treatment are used to minimize problems
and assure efficient and reliable operation of cooling
water systems. Each open recirculating cooling system
is unique. Among those characteristics that make one
system different from another are:
- System design, including
size, basin depth, materials of construction, flow
rates, heat transfer rates, temperature drop and other
factors.
- Water, including make-up
water composition, pretreatment and cycles of concentration.
- Blowdown water discharge
restrictions.
The selection
of a treatment program for a specific system must take
into account all of these system characteristics and
others, and must contain materials to control, to an
acceptable degree, each of the potential problems that
may occur in that system. It is fortuitous that many
of the chemicals used to treat cooling systems are effective
in controlling more than one problem. For example, some
carbon steel corrosion inhibitors also effectively control
calcium carbonate scale.
(1) Corrosion
Inhibition
Carbon
steel is commonly used because of its favorable cost
and good mechanical properties. Many other alloys are
employed where their mechanical and thermal properties,
and/or their corrosion resistance are required.
Corrosion
inhibitors are almost universally used to control deterioration
of carbon steel and other alloys in cooling systems.
Corrosion inhibitors work by interfering with chemical
reactions of metals with aqueous environment. They may
restrict either the anodic or the cathodic at the anodes
are called anodic inhibitors and inhibitors that work
at the cathodes are called cathodic inhibitors. Many
different types of chemicals are employed as corrosion
inhibitors. The effectiveness of nay specific inhibitor
composition, and the quantities required for good results,
depend upon the conditions in each specific system.
Most practical
corrosion inhibitor programs employ combinations of
two or more compounds. Anodic and cathodic inhibitors
are often used together to establish control over both
sides of corrosion reaction. Such mixtures are said
to be synergistic when the performance of the mixture
is seen to be greater than the performance expected
from the individual compounds added together. Because
of this effect, some inhibitors that are known to be
weak when used alone, can make important, cost-effective
contributions to corrosion control when used in combinations
with other inhibitors. For more details, please discuss
with the manufacturers of corrosion inhibition chemicals.
The corrosion control due to MIC is discussed here.
No discussion
of corrosion control in open recirculating cooling systems
would be complete without mention of microbiologically
induced corrosion. MIC is recognized as a major source
of under-deposit pitting attack in many systems that
are otherwise well protected against corrosion. All
of the metals and alloys are subject to MIC, and many
corrosion failures in alloys previously thought to be
corrosion-resistant in open cooling water environments
are not recognized as MIC related.
MIC does
not, in general, involve direct attack of bacteria on
metal. Rather, MIC refers to corrosion that is induced
or accelerated by the presence of products of microbiological
metabolism. The most commonly seen cases of MIC are
caused by sulfate-reducing bacteria. These are anaerobic
bacteria that cannot live in the presence of dissolved
oxygen in cooling water. They exist under deposits of
corrosion products, suspended solids or biological slimes.
They obtain their metabolic energy by reducing sulfate
ions in the water and forming hydrogen sulfide(H2S)
or metal sulfide salts. The corrosion process generates
more deposit and the process accelerates. Since the
process is anaerobic (oxygen free), corrosion resistant
films that depend on dissolved oxygen in the cooling
water break down. This leads, eventually, to deep pitting
attack.
Other bacteria
can also cause MIC to occur. Acid-producing bacteria,
also anaerobic in nature, form organic acids under-deposits.
These acids can attack carbon steel and other metals
ad alloys, producing the characteristic pitting attack.
Iron-oxidizing bacteria react with ferrous (reduced)
iron in cooling water and form voluminous deposits of
mixed iron oxides and biological slimes, under which
sulfate reducing and acid-producing bacteria can grow.
Detection
and recognition of MIC in operating cooling water systems
involves the use of several different techniques. Common
microbiological assays of planktonic (free swimming)
bacteria in the cooling water are not a useful way to
detect the presence of MIC-causing bacteria. A cooling
system can show very low levels of planktonic bacteria
and still be severely contaminated with anaerobic sulfate-reducers
and other bacteria living in and under deposits. It
is essential to use spool pieces and other test devices
that can allow sessile (attached) bacteria to grow and
to inspect the cooling tower, heat exchangers and low-flow
points in the system regularly for the presence of biological
deposits. Field test kits are available that can detect
the presence of sulfate-reducing bacteria in fresh deposits
removed from operating cooling systems, and in some
cases, a metallographic examination can show corrosion
patterns characteristic of certain types of MIC-causing
bacteria.
The first
line of defense in protecting cooling systems from MIC
must be to keep the system clean and free of deposits.
With the system clean, a microbiocide program must be
selected which is effective under the operating conditions
in the system and compatible with the water chemistry
and with other treatment programs in use. Finally, the
system must be monitored regularly to detect any appearance
of biological or other deposit that can encourage anaerobic
bacteria to grow. Microbiological control methods are
discussed in detail in another part of this manual.
(2) Scale
Inhibitions
Five general
methods are available for controlling mineral scale
formation in open recirculating cooling systems. These
are:
- External pretreatment
of the make-up water
- External side stream or
full flow treatment of the circulating water
- Blowdown control
- Chemical treatment of
the circulating water to reduce the reactivity of
one of more reacting species
- Chemical treatment of
the circulating water to "stabilize" reactive
species so that they will not precipitate from solution.
The optimum
scale control program developed for any specific system
must depend on the make-up water composition and its
availability, operating parameters in the cooling systems,
the number of concentration cycles to be carried in
the circulating water, and sometimes on effluent considerations.
Some systems, for which plenty of very soft make-up
water is available, do not require any scale control
program. For other systems, simple stabilization chemical
treatment is sufficient. On the other hand, in many
parts of the country the make-up water is both hard
and in short supply, so that it must be conserved. The
most cost-effective scale control program for recirculating
cooling systems in such cases may include, for example,
partial softening of the make-up water, strict control
of concentration cycles, side stream filtration or softening
and stabilization chemical treatment of the circulating
water. For further chemical treatment, contact the makers
of chemicals. The blowdown control shall be only discussed
here.
Increasing
the blowdown rate from a recirculating cooling system
is a simple way to reduce the levels of calcium and
alkalinity in the water, thus reducing the calcium carbonates
scaling potential. However, this is frequently not a
cost-effective option. Increased blowdown, which means
operating the cooling system at lower cycles of concentration,
requires increased make-up water and products more wastewater
for disposal. Increased make-up leads to increased corrosion
inhibitor usage and may require more frequent biocide
applications.
Blowdown
control is, however, a critical part of any good scale
control program in open recirculating cooling systems.
It is important to strike a technically practical and
cost-effective balance between the hardness that can
be removed from the make-up water by pretreatment, the
cycles of concentration that can normally be achieved,
the amount and quality of blowdown water that can be
tolerated and the costs of acid and stabilizing treatment
chemicals. The ability of the plant to control the system
is also an important factor. Widely varying blowdown
rates can make any scale control program costly and/or
ineffective. Also, lapses in feed of stabilizing chemicals
can lead to serious scaling problems if the system is
operating under supersaturated conditions.
(3) Suspended
Solid Control
Water-borne
suspended solids, as defined here, includes silt and
clay, corrosion products and other metal oxides,
and insoluble process contaminates, but not biologically
active solids. Treatments for controlling deposition
of these materials are developed based on experience
and empirical data, since the materials are heterogeneous
and poorly defined. Physical characteristic, such as
particle size and density, and surface properties, including
electrical charge, are probably more significant than
chemical compositions. Progress is being made in understanding
dispersion chemistry in aqueous systems and this is
leading to the development of new and better dispersants.
It does not seem likely, however, that dispersion chemistry
will, in the near future, reach the level of technical
sophistication now achieved for corrosion and scale
control in cooling water systems.
(4) Microbiological
Growth Control
The purpose
of this technical manual is to explain how to control
the microbiological growth in the cooling water systems.
This will be discussed from the next chapter.
4) Performance Monitoring
& Chemical Analysis
The success
of the chemical treatment program is often dictated
by the reliability and accuracy of the chemical feed
system. Chemical feed systems can be as simple as operator
sampling and testing for each control parameters, followed
by manual addition of the proper chemical at the proper
dosage, or it can involve full computer control for
measurement and adjustment of all chemicals included
in the treatment program. It is important to remember
that operators are the most important element of the
treatment program. They must have a complete understanding
of the treatment program and how the use of each chemical
affects the cooling water system performance. Operators
must know how their chemical feed system operates in
order to recognize whether or not it is working properly.
Also, a chemical feed system needs periodic maintenance
and responsibility to recognize when maintenance is
needed.
|