|    
                          1) Flexible Connector Line 
                        This line is used to connect 
                          the isolating valve of container cylinder to the header 
                          valve in the manifold header pipe and is made of Cadmium 
                          plated copper flexible tubing (1/4" OD x 6' or 
                          10' length). The isolating valve assembly will trap 
                          the gas in the flexible connector when replacing the 
                          gas containers/cylinders, and prevent moisture from 
                          entering the line. Moisture inside of flexible connector 
                          combined with gas will cause corrosion. Keep isolating 
                          valves closed when changing the gas containers/cylinders. 
                          When replacing flexible connectors, the header valves 
                          if possible should be closed to prevent gas from escaping 
                          and moisture from entering the manifold. Header valve 
                          permits isolating the flexible connector from the manifold 
                          piping for maintenance or replacement. 
                        2) Pressure Manifold Line 
                        The pressure manifold allows 
                          for the coupling of any number of chlorine containers/cylinders 
                          to a common header as required for a gas feed system. 
                          The valves on horizontal manifolds may be piped in either 
                          direction. The maximum size of a chlorine header system 
                          under pressure in any applications should never be larger 
                          than one (1) inch. The pipes size & materials are 
                          as ff.: 
                        
                          - 3/4" seamless carbon 
                            steel, grade B, Sch. 80, types S, ASTM A-106 pipe 
                            for Gas Withdrawal
 
                          - 1" seamless carbon 
                            steel, grade B, ASTM A-106 pipe for Liquid Withdrawal
 
                         
                        Note that prior to assembly, 
                          the threads of header valves should be coated with a 
                          mixture of litharge and glycerin for a permanent joint 
                          or Teflon tape for a serviceable connection to above 
                          manifold pipe. 
                        The entire length of the 
                          chlorine gas pressure manifold should be heat traced 
                          with strip heaters to prevent reliquefaction of chlorine 
                          gas in the manifold. Drip legs with pad heaters should 
                          also be supplied. The number and orientation of the 
                          drip legs should be in accordance with Engineering Data 
                          Sheets A2.62107 and A2.62108. 
                        In preparation for use, all 
                          chlorine pressure piping should be pressure tested. 
                          Hydrostatic testing of piping requires extensive drying 
                          before chlorine introduction. This can be done by passing 
                          steam through the lines, from the high end, until the 
                          lines are thoroughly heated. Disconnect the steam source 
                          and thoroughly drain all low spots and pockets. With 
                          the lines still warm, blow dry air, dew point -40oC 
                          through the lines until they are dry. This may require 
                          several hours. After drying, pressure test with dry 
                          air or nitrogen to 150 psig. 
                        3) Vacuum Line 
                        With remote mounted ejectors, 
                          the optimum size of the vacuum line is of prime concern 
                          since the gas feeder operation is entirely dependent 
                          upon the vacuum created by the ejector. The maximum 
                          and minimum vacuum levels created by the ejector should 
                          be: 
                        
                          - Maximum Level: 22 - 23" 
                            Hg
 
                          - Minimum Level: 8 - 10" 
                            Hg
 
                         
                        A minimum of 10" Hg 
                          allows purging of entrained air or gas that may accumulate 
                          in the solution lines. The vacuum line connecting the 
                          gas feeder components is normally designed for a total 
                          friction loss of 1.5 - 1.75" Hg at 68oF 
                          with a 22 - 23" Hg vacuum level at the ejector. 
                        
                           
                            |  
                               Vacuum Line Size Requirements  | 
                           
                           
                            |   Max. 
                                Gas Feed Rate  | 
                              30m  | 
                              60m  | 
                              100m  | 
                              200m  | 
                              300m  | 
                              400m  | 
                              500m  | 
                           
                           
                            |   1 
                                kg/h  | 
                              3/8"  | 
                              3/8"  | 
                              1/2"  | 
                              1/2"  | 
                              1/2"  | 
                              5/8"  | 
                              5/8"  | 
                           
                           
                            |   2 
                                kg/h  | 
                              3/8"  | 
                              1/2"  | 
                              5/8"  | 
                              5/8"  | 
                              3/4"  | 
                              3/4"  | 
                              3/4"  | 
                           
                           
                            |   4 
                                kg/h  | 
                              1/2"  | 
                              5/8"  | 
                              3/4"  | 
                              3/4"  | 
                              1"  | 
                              1"  | 
                              1"  | 
                           
                           
                            |   10 
                                kg/h  | 
                              5/8"  | 
                              3/4"  | 
                              1"  | 
                              1"  | 
                              1-1/4"  | 
                              1-1/4"  | 
                              1-1/4"  | 
                           
                           
                            |   20 
                                kg/h  | 
                              1  | 
                              1-1/4  | 
                              1-1/4  | 
                              1-1/2  | 
                              1-1/2  | 
                              1-1/2  | 
                              2  | 
                           
                           
                            |   40 
                                kg/h  | 
                              1  | 
                              1-1/4  | 
                              1-1/2  | 
                              2  | 
                              2  | 
                              2  | 
                              2  | 
                           
                           
                            |   75 
                                kg/h  | 
                              1-1/2  | 
                              2  | 
                              2  | 
                              2-1/2  | 
                              2-1/2  | 
                              3  | 
                              3  | 
                           
                           
                            |   120 
                                kg/h  | 
                              2  | 
                              2  | 
                              2-1/2  | 
                              2-1/2  | 
                              3  | 
                              3  | 
                              3-1/2  | 
                           
                           
                            |   150 
                                kg/h  | 
                              2  | 
                              2-1/2  | 
                              3  | 
                              3  | 
                              3-1/2  | 
                              4  | 
                              4  | 
                           
                           
                            |   190 
                                kg/h  | 
                              2-1/2  | 
                              3  | 
                              3  | 
                              3-1/2  | 
                              4  | 
                              4  | 
                              4-1/2  | 
                           
                           
                            |   Note. 
                                The data presented is based on upon calculation 
                                so the total system friction loss in piping does 
                                not exceed 5" water column.   | 
                           
                         
                        The design procedure steps 
                          for determining vacuum lines are some complex since 
                          the optimum pipe size for vacuum lines between the chlorinator 
                          and the ejector is subject to a great deal of scrutiny, 
                          but we use the maker's suggested sizing table. In general, 
                          the vacuum line is recommended to use a flexible tube 
                          of high density polyethylene for up to 5/8" and 
                          Sch. 80 PVC Pipe for larger than 5/8". 
                        4) Solution Line 
                        The piping downstream from 
                          the ejector is the chlorine solution line. It is permissible 
                          to manifold the ejector discharge from two or more chlorinators 
                          into one point of application (Provided the solution 
                          line discharges into a multiple diffuser system so that 
                          there is one diffuser per ejector.), but a solution 
                          line to the point of disinfection should not be manifolded 
                          to any other point of application. The most desirable 
                          arrangement is for each ejector to have its own solution 
                          line and diffuser. The bubbles of gas, which release 
                          a tremendous amount of carbon dioxide and other gases 
                          when some water is carrying a chlorine solution, in 
                          the solution passing through the rotometer can cause 
                          sufficient vibration to severely limit the accuracy 
                          of the reading. Glass tube rotometers should not be 
                          used because this vibration can cause the rotometer 
                          float to shatter the glass tube. The only rotometers 
                          satisfactory for chlorine solution lines are the straight 
                          through metal (Hastelloy C) or PVC tube type with dial 
                          indication. 
                        The amount of water required 
                          must be sufficient to limit the chlorine solution strength 
                          to 3,500 ppm. The excess concentrated solution (molecular 
                          chlorine breaking out of solution) can cause fuming 
                          at the point of application if open to the atmosphere, 
                          and gas binding in solution lines under low negative 
                          heads. A broad rule of thumb is 40 gal of water/day/pound 
                          of chlorine. 
                        Solution line lengths should 
                          be kept to an absolute minimum. The correct diameter 
                          of a solution line is determined by: 
                        
                          - Rate of solution flow 
                            of (ejector outlet)
 
                          - Allowable friction loss. 
                            Generally the friction loss must be kept low so the 
                            back pressure at the outlet of the ejector is not 
                            increased.
 
                         
                        From the point forward of 
                          ejector, a corrosive chlorine solution will be encountered 
                          which requires special materials. The chlorine solution 
                          lines can be either three types of pipes, which are 
                          commonly used for solution service under normal temperature 
                          conditions (below 100oF). These are: 
                        
                          - Sch. 80 PVC pipe, Grade 
                            A, Type 1 for smaller than 6" size.
 
                          - Sch. 40 rubber lined black 
                            steel pipe for larger than 6" size or where is 
                            required a rigid pipe.
 
                          - Rubber Hose for strong 
                            chemical solution: Suitable troughs are required for 
                            support and protection. Where hose is likely to be 
                            subjected to any appreciable negative head, it should 
                            be internally reinforced to prevent collapsing. Hose 
                            is available in two general types:
 
                         
                        * Wrapped hose is available 
                          in lengths up to 50 feet and all common sizes through 
                          2" inside diameter. Larger sizes are available 
                          on special order. This type of hose can be reinforced 
                          externally against pressure or internally to prevent 
                          collapse. 
                        * Molded hose is available 
                          in longer continuous lengths and all common sizes up 
                          to and including 1-1/2" inside diameter. 
                        Valves on the solution lines 
                          can be either diaphragm or ball type. Diaphragm types 
                          are usually flanged, rubber lined, or PVC-lined cast 
                          iron Saunders-type valves. The ball type PVC valve is 
                          preferable up to 2-1/2" size, although the ball 
                          type valve is available in much larger sizes. The diaphragm 
                          type should be considered for sizes 3" and larger. 
                        5) Diffuser Pipe Line 
                        There are so many types of 
                          diffusers, but the perforated diffuser and pipeline 
                          diffuser are usually applied to the mixing of chlorine 
                          solution and cooling water in basin. 
                        
                          - Perforated Diffusers: 
                            The pipe is perforated, so that chlorine solution 
                            is discharged mostly below the minimum water surface 
                            level. This diffuser eliminates the problem of the 
                            accumulation of debris which is always prone to collect 
                            on any object projecting into the flowing cooling 
                            water. The diffuser should be designed to be easily 
                            removed with the flanged connection. This may be necessary 
                            to clean the slot of slit and other debris as well 
                            as to inspect for plugging of perforations. 
 
                             
                            Experience indicates that over a period of three or 
                            four years chlorine solution diffusers do plug up 
                            in cooling tower application. The deposits that cause 
                            the trouble appear to be the result of highly chlorinated 
                            organic compounds containing a large portion of grease, 
                            which provides a waxi like binder. 
                           
                          - Pipeline Diffusers: This 
                            is well known that the best mixing occurs when the 
                            chlorine solution is discharged into the center of 
                            the pipe, this is not practical because of the debris 
                            that will accumulate on the projected diffuser. Therefore 
                            the diffuser must end flush with the inside wall of 
                            the conduit, but it should be designed for a velocity 
                            of 22 - 26 feet/sec in order to project the chlorine 
                            solution toward the center of the pipe. This velocity 
                            across the diffuser orifice will result in an 8 - 
                            10 feet pressure drop. Therefore the chlorine solution 
                            line and ejector water supply will have to be designed 
                            to accommodate this additional ejector back- pressure.
 
                             
                            It is reasonable to locate the diffuser pipe line 
                            front the screens of the sump fits of cooling water 
                            circulation pump for the best mixing in the cooling 
                            tower basin. Static pressure at the discharge of ejector 
                            should be limited to no more than 4 - 5 psi, for the 
                            following reasons: (1) Ejector operating pressures 
                            and water quantity escalate rapidly as the back pressure 
                            on the ejector rises beyond 5 psi. particularly when 
                            the chlorine feed rate is in excess of 500 lb/day 
                            (For chlorinator 500 lb/day and smaller this back 
                            pressure limitation is not a factor.). (2) Head loss 
                            through the diffuser is used as a chlorine mixing 
                            devices. Allow 8 - 10 feet loss through the diffuser 
                            for this function. To meet this requirement ejector 
                            must be located as close to the diffuser as possible. 
                         
                        The diffuser has a negative 
                          head in most cases of the cooling tower application. 
                          If it is not properly designed and anytime a negative 
                          head exists in the chlorine solution line, molecular 
                          chlorine will break out of the chlorine solution and 
                          cause serious gas emission at the diffuser. 
                        Therefore, if the cooling 
                          water level at diffuser is below ejector throat, the 
                          hydraulic gradient from the ejector to the diffuser 
                          must be calculated to provide a reasonable ejector back-pressure. 
                          Assume this back-pressure is 5 ft (approx. 2 psi). Then 
                          the friction loss through the diffuser holes + (plus) 
                          the line losses - (minus) the difference in elevation 
                          between water level and ejector throat must equal approximately 
                          5 ft of head of previously mentioned back pressure. 
                          This is one of the reasons for having a compound gage 
                          on the solution line at the discharge of ejector. 
                        The diffusers are customarily 
                          made up of Sch. 80 PVC pipe and fittings. If the specifications 
                          for underwater piping require steel construction for 
                          additional strength, all the diffuser piping must be 
                          made of rubber-lined and rubber-covered steel pipe. 
                          The diffuser holes must also be rubber-covered. Nuts 
                          and bolts for assembly of the underwater portion should 
                          be 316 stainless steel. The diameter of diffuser pipe 
                          must be no less than the ejector outlet size and in 
                          some cases may be larger, since a negative head will 
                          be to create a siphoning action. The optimum size of 
                          perforated holes (orifices) and the number of holes 
                          per feet must be carefully considered. 
                             |