Many important design provisions for chlorination building 
                    relate to the safe use of chlorine and the protection of those 
                    working with it. Chlorinator rooms should be at or above ground 
                    level and Container storage should be planned so that it is 
                    separate from chlorinators and accessories. It is logical 
                    to locate the chlorination room near the point of application 
                    to minimize the length of chlorine line for reducing the possibility 
                    of reliquefaction at the pressure gas manifold & chlorinator. 
                    Other general site considerations include a location which 
                    permits ease of access to facilitate container transport and 
                    handling, adequate drainage, and separation from other work 
                    areas. 
                  1) Separation 
                  Proper design standards require 
                    either a completely separate chlorination building or a room 
                    completely separate from the remainder of the building with 
                    access only through an outside door. There should be no apertures 
                    of any type from the chlorination room to other parts of a 
                    common building through which chlorine gas could enter other 
                    work areas. 
                  2) Fire Hazard 
                  The building should be designed 
                    and constructed to protect all elements of the chlorine system 
                    from fire hazard. If flammable materials are stored in the 
                    same building, a fire wall should separate the two areas. 
                    Fire-resistive construction is recommended. Water should be 
                    readily available for cooling containers/cylinders in case 
                    of fire. 
                  3) Space Requirements 
                  Modern chlorination equipment is 
                    available in modules so that the chlorinators and accessory 
                    equipment can be arranged in a skid mounting type. There should 
                    be about four feet between the front of a module and the nearest 
                    wall and about two feet on the sides and rear. There should 
                    be adequate room provided to allow ready access to all equipment 
                    for maintenance and repair. There should be sufficient clearance 
                    to allow safe handling of equipment containers. 
                  4) Ventilation 
                  Adequate forced air ventilation 
                    is required for all chlorine equipment rooms. An exception 
                    to this would be small chlorinator installation (less than 
                    100 lb/day) located in separate buildings if the windows and 
                    doors can provide the proper cross-circulation. For a small 
                    building, windows in opposite walls, a door with a louver 
                    near the floor, and a rotating- type vent in the ceiling usually 
                    provide the necessary cross-ventilation. 
                  Factors to be considered in the 
                    design of a ventilation system are: air turnover rate, exhaust 
                    system type and location, intake location and type, electrical 
                    controls, and temperature control. A forced air system should 
                    be capable of providing one complete air change in 2-5 minutes. 
                    Since chlorine gas is 2-1/2 times heavier than air, it is 
                    logical to provide air inlet openings for ventilation fans 
                    at or near floor level. (Room ventilation air should always 
                    enter at floor level and exit at ceiling or roof level, because 
                    vapor leaks will always followed by the air circulation path.) 
                  For small installation it is common 
                    to employ an exterior exhaust fan with the intake duct extending 
                    to the chlorine room floor. A wall-type exhaust fan is an 
                    acceptable alternative. The exhaust system should be completely 
                    separate from any other ventilation system. For larger installations 
                    a blower-type fan is needed. The use of free-moving, gravity-operated 
                    louvers may be advantageous in colder climates for conserving 
                    room heat when the blowers are not in operation; however, 
                    venting systems should not have covers. The fan discharge 
                    should be located so as to not contaminate the air supply 
                    of any other room or nearby habitations. It is mandatory that 
                    the ventilation discharge be located at a high enough elevation 
                    to assure atmospheric dilution, e.g., at the roof of a single-story 
                    building. 
                  Air inlets should be so located 
                    as to provide cross-ventilation. To prevent a fan from developing 
                    a vacuum in the room and thereby making it difficult to open 
                    the doors, louvers should be provided above the entrance door 
                    and opposite the fan suction. In some cases, it may be necessary 
                    to provide temperature control on the air supply so that the 
                    chlorination system is not adversely affected. A signal light 
                    indicating fan operation should be provided at each entrance 
                    when the fan can be controlled from more than one point. 
                  5) Wind Socks 
                  All installations should locate 
                    at lest one wind sock on the chlorine supply structure. This 
                    is very valuable in the event of a leak. The sock should be 
                    as high as possible. 
                  6) Doors 
                  Exit doors from the chlorination 
                    room should be equipped with emergency hardware and open outward. 
                    Some design guides recommend two means of exit from each room 
                    or building in which chlorine is stored, handled, or used; 
                    this would not appear to be essential in most cases. 
                  7) Inspection Windows 
                  A means should be provided which 
                    permits viewing of the chlorinator and other equipment in 
                    the chlorination room without entering the room. A clear-glass, 
                    gastight window which is installed in an exterior door or 
                    interior wall of the room is recommended. Door windows appear 
                    to be a logical provision even with a separate wall inspection 
                    window. 
                  8) Heating 
                  The chlorinator room should be 
                    provided with a means for heating and controlling room air 
                    temperature above 55oF. A minimum room temperature 
                    of 60oF has been recommended as a good practice. 
                    Ideally, the heating system should be able to reliably maintain 
                    a uniform moderate temperature throughout the chlorination 
                    room. Hot water heating is generally preferred because of 
                    safety considerations and the uniformity of temperature which 
                    this method of heating provides, without the extremes which 
                    might be experienced with failure of a steam heating system. 
                    Electric heating is suitable, and forced air heating would 
                    be appropriate if an independent system is provided for the 
                    chlorination room or building. Central hot air heating is 
                    not acceptable since gas could escape through the heating 
                    system. 
                  Chlorine vapor leaving a container/cylinder 
                    will condense if the piping temperature is significantly lower 
                    than the temperature of container/cylinder. The design should 
                    provide a higher temperature in the chlorinator room than 
                    in container/cylinder room. This applies to systems using 
                    the gas phase from the containers/cylinders. Elimination of 
                    unnecessary windows may aid in maintaining uniform building 
                    temperatures. The minimum allowable temperature for the chlorine 
                    storage room area is about 50oF. Below this temperature 
                    the flow of chlorine becomes sluggish and erratic, particularly 
                    for small installations, from 1 to 20 lb/day. Heat should 
                    never be applied directly to a chlorine container/cylinder. 
                    Steel will ignite spontaneously at about 483oF 
                    in the presence of chlorine. 
                  If the storage area for in-service 
                    containers/cylinders is properly designed, external chlorine 
                    pressure- reducing valves are not required. If the location 
                    of these containers/cylinders is remote, an external reducing 
                    valve should be installed as close as possible to the containers/cylinders. 
                    (When remote vacuum systems are used, external pressure reducing 
                    valves may be required to provide a two-step pressure reduction 
                    owing to ambient conditions.) 
                  9) Drains 
                  It is generally desirable to keep 
                    the plant floor drain system separate from that of chlorinator. 
                    Drainage from a chlorinator drain relief valve may contain 
                    chlorine. Consequently, hose, plastic pipe, or tile drains 
                    are recommended. The discharge should be delivered to a point 
                    beyond a water-sealed trap or disposed of separately where 
                    there is ample dilution. 
                  Scale pits are generally designed 
                    with floor drains having a water-sealed trap. In actual practice 
                    most traps do not contain enough water to form a seal, and 
                    it would be preferable to provide a straight pipe drain outside 
                    to grade. 
                  10) Vents 
                  Chlorinators, external pressure-reducing 
                    valve, remote vacuum systems, and automatic switchover systems 
                    have vents to atmosphere. Since the advent of the 1988 Uniform 
                    Fire Code, (UFC) these vents cannot necessarily be allowed 
                    to discharge directly to the outside air as has been practiced 
                    since the use of vacuum operated chlorinators. This represents 
                    a span of 70 years without any damaging results because chlorine 
                    vapor emissions (as opposed to liquid spills) are diluted 
                    quickly by the ambient air. Dealing with these vents to comply 
                    with the UFC. 
                  These vents lines must be piped 
                    in such a manner that moisture is not allowed to accumulate 
                    in the piping. This means that some will have to be equipped 
                    with a condensate trap if the piping cannot be arranged to 
                    allow the moisture to drain from the vent line. Those vents 
                    that are required to "Breathe" should be fitted 
                    with a wire screen at the discharge end to prevent the usual 
                    invasion of insets. 
                  In all cases, manufacturers' instructions 
                    should be followed closely regarding piping requirements. 
                    It is acceptable to run the vent vertically (but no more than 
                    25 feet) above the location of the unit that vents. 
                  11) Electrical 
                  Controls for fans and lights should 
                    operate automatically when the door is opened, and there should 
                    be provisions to active these manually from outside the room. 
                    Switches for fans and lights should be outside of the room 
                    at the entrance. A signal light indicating fan operation should 
                    be provided at each entrance when the fan can be controlled 
                    from more than one point. 
                       |