Many important design provisions for chlorination building
relate to the safe use of chlorine and the protection of those
working with it. Chlorinator rooms should be at or above ground
level and Container storage should be planned so that it is
separate from chlorinators and accessories. It is logical
to locate the chlorination room near the point of application
to minimize the length of chlorine line for reducing the possibility
of reliquefaction at the pressure gas manifold & chlorinator.
Other general site considerations include a location which
permits ease of access to facilitate container transport and
handling, adequate drainage, and separation from other work
areas.
1) Separation
Proper design standards require
either a completely separate chlorination building or a room
completely separate from the remainder of the building with
access only through an outside door. There should be no apertures
of any type from the chlorination room to other parts of a
common building through which chlorine gas could enter other
work areas.
2) Fire Hazard
The building should be designed
and constructed to protect all elements of the chlorine system
from fire hazard. If flammable materials are stored in the
same building, a fire wall should separate the two areas.
Fire-resistive construction is recommended. Water should be
readily available for cooling containers/cylinders in case
of fire.
3) Space Requirements
Modern chlorination equipment is
available in modules so that the chlorinators and accessory
equipment can be arranged in a skid mounting type. There should
be about four feet between the front of a module and the nearest
wall and about two feet on the sides and rear. There should
be adequate room provided to allow ready access to all equipment
for maintenance and repair. There should be sufficient clearance
to allow safe handling of equipment containers.
4) Ventilation
Adequate forced air ventilation
is required for all chlorine equipment rooms. An exception
to this would be small chlorinator installation (less than
100 lb/day) located in separate buildings if the windows and
doors can provide the proper cross-circulation. For a small
building, windows in opposite walls, a door with a louver
near the floor, and a rotating- type vent in the ceiling usually
provide the necessary cross-ventilation.
Factors to be considered in the
design of a ventilation system are: air turnover rate, exhaust
system type and location, intake location and type, electrical
controls, and temperature control. A forced air system should
be capable of providing one complete air change in 2-5 minutes.
Since chlorine gas is 2-1/2 times heavier than air, it is
logical to provide air inlet openings for ventilation fans
at or near floor level. (Room ventilation air should always
enter at floor level and exit at ceiling or roof level, because
vapor leaks will always followed by the air circulation path.)
For small installation it is common
to employ an exterior exhaust fan with the intake duct extending
to the chlorine room floor. A wall-type exhaust fan is an
acceptable alternative. The exhaust system should be completely
separate from any other ventilation system. For larger installations
a blower-type fan is needed. The use of free-moving, gravity-operated
louvers may be advantageous in colder climates for conserving
room heat when the blowers are not in operation; however,
venting systems should not have covers. The fan discharge
should be located so as to not contaminate the air supply
of any other room or nearby habitations. It is mandatory that
the ventilation discharge be located at a high enough elevation
to assure atmospheric dilution, e.g., at the roof of a single-story
building.
Air inlets should be so located
as to provide cross-ventilation. To prevent a fan from developing
a vacuum in the room and thereby making it difficult to open
the doors, louvers should be provided above the entrance door
and opposite the fan suction. In some cases, it may be necessary
to provide temperature control on the air supply so that the
chlorination system is not adversely affected. A signal light
indicating fan operation should be provided at each entrance
when the fan can be controlled from more than one point.
5) Wind Socks
All installations should locate
at lest one wind sock on the chlorine supply structure. This
is very valuable in the event of a leak. The sock should be
as high as possible.
6) Doors
Exit doors from the chlorination
room should be equipped with emergency hardware and open outward.
Some design guides recommend two means of exit from each room
or building in which chlorine is stored, handled, or used;
this would not appear to be essential in most cases.
7) Inspection Windows
A means should be provided which
permits viewing of the chlorinator and other equipment in
the chlorination room without entering the room. A clear-glass,
gastight window which is installed in an exterior door or
interior wall of the room is recommended. Door windows appear
to be a logical provision even with a separate wall inspection
window.
8) Heating
The chlorinator room should be
provided with a means for heating and controlling room air
temperature above 55oF. A minimum room temperature
of 60oF has been recommended as a good practice.
Ideally, the heating system should be able to reliably maintain
a uniform moderate temperature throughout the chlorination
room. Hot water heating is generally preferred because of
safety considerations and the uniformity of temperature which
this method of heating provides, without the extremes which
might be experienced with failure of a steam heating system.
Electric heating is suitable, and forced air heating would
be appropriate if an independent system is provided for the
chlorination room or building. Central hot air heating is
not acceptable since gas could escape through the heating
system.
Chlorine vapor leaving a container/cylinder
will condense if the piping temperature is significantly lower
than the temperature of container/cylinder. The design should
provide a higher temperature in the chlorinator room than
in container/cylinder room. This applies to systems using
the gas phase from the containers/cylinders. Elimination of
unnecessary windows may aid in maintaining uniform building
temperatures. The minimum allowable temperature for the chlorine
storage room area is about 50oF. Below this temperature
the flow of chlorine becomes sluggish and erratic, particularly
for small installations, from 1 to 20 lb/day. Heat should
never be applied directly to a chlorine container/cylinder.
Steel will ignite spontaneously at about 483oF
in the presence of chlorine.
If the storage area for in-service
containers/cylinders is properly designed, external chlorine
pressure- reducing valves are not required. If the location
of these containers/cylinders is remote, an external reducing
valve should be installed as close as possible to the containers/cylinders.
(When remote vacuum systems are used, external pressure reducing
valves may be required to provide a two-step pressure reduction
owing to ambient conditions.)
9) Drains
It is generally desirable to keep
the plant floor drain system separate from that of chlorinator.
Drainage from a chlorinator drain relief valve may contain
chlorine. Consequently, hose, plastic pipe, or tile drains
are recommended. The discharge should be delivered to a point
beyond a water-sealed trap or disposed of separately where
there is ample dilution.
Scale pits are generally designed
with floor drains having a water-sealed trap. In actual practice
most traps do not contain enough water to form a seal, and
it would be preferable to provide a straight pipe drain outside
to grade.
10) Vents
Chlorinators, external pressure-reducing
valve, remote vacuum systems, and automatic switchover systems
have vents to atmosphere. Since the advent of the 1988 Uniform
Fire Code, (UFC) these vents cannot necessarily be allowed
to discharge directly to the outside air as has been practiced
since the use of vacuum operated chlorinators. This represents
a span of 70 years without any damaging results because chlorine
vapor emissions (as opposed to liquid spills) are diluted
quickly by the ambient air. Dealing with these vents to comply
with the UFC.
These vents lines must be piped
in such a manner that moisture is not allowed to accumulate
in the piping. This means that some will have to be equipped
with a condensate trap if the piping cannot be arranged to
allow the moisture to drain from the vent line. Those vents
that are required to "Breathe" should be fitted
with a wire screen at the discharge end to prevent the usual
invasion of insets.
In all cases, manufacturers' instructions
should be followed closely regarding piping requirements.
It is acceptable to run the vent vertically (but no more than
25 feet) above the location of the unit that vents.
11) Electrical
Controls for fans and lights should
operate automatically when the door is opened, and there should
be provisions to active these manually from outside the room.
Switches for fans and lights should be outside of the room
at the entrance. A signal light indicating fan operation should
be provided at each entrance when the fan can be controlled
from more than one point.
|