|    
                          1) Reaction Chemistry 
                        A chlorine leak in the room 
                          housing the chlorine cylinders / containers / tanks 
                          or in the chlorinator room should be neutralized by 
                          means of neutralizing solution (Soda, Sodium Hyposulphite). 
                          Mainly caustic soda solution (NaOH) is used for neutralization 
                          of chlorinated air. 
                        The chemical reaction of 
                          chlorinated air and caustic soda (Sodium Hydroxide) 
                          is: 
                        Cl2 + 2NaOH 
                          + H2O = NaCl + NaOCl + 2H2O + 
                          44,600 Btu/mole Cl2 
                        Through the contact of chlorinated 
                          air and neutralization solution, the concentration of 
                          exhausted air could be reduced to 1ppm. Two moles of 
                          sodium hydroxide (80 pounds) is required to neutralize 
                          each mole of chlorine (70.9 pounds). The amount required 
                          to neutralize the 1 pound of leaked Cl2 is 
                          obtained by the below formula; 
                        NaOH = 80.0 / 70.9 = 1.13 
                          times to Cl2 
                        The 20% by weight of sodium 
                          hydroxide is usually used to neutralize the chlorine 
                          gas considering the freezing point in the winter. Fig. 
                          9-1 is showing the relationship between the temperature 
                          and percent of NaOH. Each gallon of 20% solution contains 
                          2.04 lbs of NaOH. 
                        2) Maximum Room Initial Concentration 
                        This is obtained from 
                        Maximum Room Initial Concentration 
                          = (Rate of Gas Vaporization / Rate of Ventilation of 
                          Blower) x 106 (ppm). 
                        3) Chlorine Concentration 
                          vs. time 
                        By performing a material 
                          balance, the following differential equation is obtained 
                          for the decrease of chlorine vapor in the room as a 
                          function of time. 
                          
                        Where, 
                          V = room volume 
                          c = Cl2 vapor concentration in room, ppm 
                          QG = room ventilation rate, ft /min 
                          t = time, min 
                        Upon integrating, the following 
                          equation is obtained: 
                          
                        Where: 
                          Ci = initial chlorine vapor concentration, 
                          ppm 
                          Co = chlorine vapor concentration at any 
                          instant, ppm 
                        4) Sump Temperature Rise 
                        Neutralization of chlorine 
                          with sodium hydroxide is an exothermic reaction. The 
                          heat of reaction is 44,600 Btu/mole of chlorine. Reaction 
                          is in liquid phase. If there is no heat loss to the 
                          air and other components of neutralization system, the 
                          temperature rise of sodium hydroxide solution can be 
                          calculated from the following equation: 
                        H = mCpDT 
                        Where, 
                          H = total heat released by reaction, BTU 
                          m = total weight of caustic solution, lb 
                          Cp =heat capacity of causitic solution, BTU/lb 
                          DT = temperature rise, oF 
                        Heat capacity for 20% by 
                          weight caustic solution is 0.9 Btu/lb. One (1) gallon 
                          of 20% NaOH is equal to 10.21 lbs. 
                        5) Chemical Utilization during 
                          Periodic Equipment Checkouts 
                        The neutralization system 
                          is a safety device to be run when the chlorine gas is 
                          leaked. Since this system is not continuously being 
                          operated, it is essential to operate the system periodically 
                          for preventing a possible malfunction of rotating parts. 
                          In general, it is highly recommended to checkout the 
                          system weekly. 
                        Carbon dioxide (CO2) 
                          will be absorbed by the caustic solution during bi-weekly 
                          testing of the system. The reaction between sodium hydroxide 
                          and carbon dioxide is: 
                        CO2 + 2NaOH = 
                          NaCO3 + H2O 
                        Two (2) moles of sodium hydroxide 
                          (80 pounds) is required to react with each mole of carbon 
                          dioxide (44 pounds). Ambient air contains 0.033% by 
                          volume (or mole) of carbon dioxide. Each mole of air 
                          at ambient conditions occupies a volume of 386 cubic 
                          feet. Therefore, 3,000 cfm of air blower is equal to 
                          7.77 moles/min. The carbon dioxide flow rate will be 
                          0.11 lbs/min. Caustic consumption for each minute of 
                          neutralization system testing is 0.21 pounds/min. If 
                          the system testing lasts 15 minutes, then the weekly 
                          caustic consumption is 3.0 pounds. After one (1) year 
                          of regular weekly check-out, the total caustic used 
                          is: 3.0 x 52 = 156 lbs/year. About 30 gal. of 50% of 
                          caustic solution has to be added into the NaOH solution 
                          tank every year. (50% caustic =6.643 lbs/gal of NaOH) 
                        6) RJ Scrubber System 
                        This scrubber system was 
                          designed to meet the Uniform Fire Code (revised 1990), 
                          Section 80.303 of Article 80 as it pertains to indoor 
                          storage of compressed gases. It was specially designed 
                          to meet the UFC maximum allowable discharge concentration 
                          of the Cl2 vapor, to one-half of IDLH (Immediate Danger 
                          to Life and Health) at the point of discharge to the 
                          outside atmosphere. For chlorine, the IDLH is 30 ppm. 
                          Therefore the maximum allowable discharge concentration 
                          in the scrubber vent stack is 15 ppm as stated in the 
                          UFC. The RJ scrubber, though, is designed to treat a 
                          release rate much higher than the UFC requirement. A 
                          full scale test with a chlorine rate at about 100 lb/min. 
                          resulted in vent stack chlorine concentrations of less 
                          than 4 ppm. The entire unit is a skid-mounted package 
                          measuring 16 feet long 8 feet wide and 8 feet high. 
                        (1) Scrubber 
                        This is a single-pass three 
                          stage absorption system that operates entirely under 
                          a vacuum (negative pressure), including all the ducting. 
                          This eliminates the possibility of any release of chlorine 
                          contaminated air. This system is shown in Fig. 9-2. 
                          The three stages of absorption consists of one horizontal 
                          spray scrubbing stage, followed by two horizontal cross-flow 
                          packed bed sections. The design of each stage provides 
                          an overall performance of 99.998% removal of the chlorine 
                          vapor in the vent discharge. This automatically guarantees 
                          that the removal efficiency on a once through basis 
                          will easily neutralize the worst-case chlorine leak 
                          occurrence. The movement of air through the scrubber 
                          is provided by a 5 HP 3000 cfm exhaust fan. 
                        (2) Caustic Storage 
                        This amounts to about 2400 
                          gallons of 20 percent NaOH solution which is about 85 
                          percent excess caustic over the theoretical requirement. 
                          This means that the maximum possible concentration of 
                          hypochlorite after the neutralization of a capacity 
                          leak would be less than 12.5 percent. 
                        (3) Activation System 
                        A chlorine leak detector 
                          activates the scrubber system in two steps: 
                        
                          -  The caustic recirculating 
                            pump is started to provide proper atomization for 
                            the first stage plus the proper wetting of the packing 
                            material in the other two stages before the exhaust 
                            fan is activated.
 
                          -  After a 5 seconds interval 
                            of step one, the 3000 cfm exhaust fan is then automatically 
                            started and this begins the scrubbing of the contaminated 
                            air. This interval before the fan is actuated is not 
                            nearly long enough to change the air pressure in the 
                            room. This automatic sequence during the initial start-up 
                            prevents the discharge of any partially treated contaminated 
                            air before the scrubber is operating at design conditions.
 
                         
                        (4) Absorption Details 
                        The absorber is located on 
                          top of caustic tank which is an integral part of the 
                          system. The caustic solution is recirculated continuously 
                          through the scrubber at the rate of 550 gpm at 25 psi 
                          which means that this is classified as a "low pressure 
                          system". The recirculating pump is 20 HP. The scrubbed 
                          air passes through a mist eliminator before it is discharged 
                          to the outside atmosphere. The discharge is monitored 
                          by an EIT series 4000, vent stack monitor. The scrubber 
                          provides a vapor residence time of 5 seconds which is 
                          much longer than in a venturi scrubber. 
                        (5) Major System Features/Advantages 
                        J has conducted full scale 
                          tests of two RJE Vapor Scrubbing Systems during April 
                          1992 at a nationally recognized testing laboratory accredited 
                          by the International Conference of Building Officials 
                          (ICBO). 
                        Testing was performed under 
                          rigidly controlled procedures with continuous on-line 
                          data recording and video taping of each of the tests. 
                          Liquid chlorine was released directly from the cylinders 
                          in a specially designed flash room (13' x 12' x 12'). 
                          The systems were evaluated with chlorine release rates 
                          from 30 lb/minute to 100 lb/minute. 
                        The Uniform Fire Code requires 
                          a maximum concentration of chlorine in the scrubber 
                          exhaust of 15 ppm. The chlorine concentration in the 
                          RJE scrubber exhausts were 2 ppm or less during all 
                          tests. 
                        In addition to proven system 
                          designs, RJE scrubber system offers many advantages 
                          that are not available with conventional systems. 
                        
                          -  Conservative Design: 
                            Although design requirements are based on the UFC 
                            release rate of 78 lb/min, the scrubber system designed 
                            for 3,000 cfm is capable of neutralizing completely 
                            more than 500 lb/min of chlorine vapor per minute 
                            on a once through basis. This could be equivalent 
                            to a complete cylinder failure with an average 20% 
                            flash-off rate.
 
                          -  Low Profile: With a special 
                            design concept, our system provides the highest scrubber 
                            performance (three stages) with very low profile. 
                            The overall system size is about 15' L x 8' W x 9' 
                            H.
 
                          -  Low Horsepower: RJE full 
                            scale system only requires about 1/2 to 2/3rd the 
                            horsepower, because of low pressure recirculation 
                            of chemicals. The table below shows the horsepower 
                            required for RJE system compared to an eductor type 
                            system.
 
                            
                               
                                |  
                                   Air Flow Rate, 
                                    cfm  | 
                                 
                                   RJE Type  | 
                                 
                                   Eductor Type  | 
                               
                               
                                |  
                                   3000  | 
                                 
                                   25  | 
                                 
                                   40  | 
                               
                               
                                |  
                                   4000  | 
                                 
                                   27.5  | 
                                 
                                   60  | 
                               
                               
                                |  
                                   5000  | 
                                 
                                   27.5  | 
                                 
                                   60 +  | 
                               
                             
                             
                          
  - Induced Draft Fan: This 
                            fan provides "negative pressure" throughout 
                            the system, including the room, ducting, and scrubber.
 
                          -  Low Pressure Recirculation: 
                            30 psig (vs. 70 psig) further enhances the safety 
                            of the system.
 
                          -  Economics: Because of 
                            the low profile and special design, this system is 
                            delivered as a completely skid mounted, piped, wired, 
                            and factory tested unit, thus reducing installation 
                            costs tremendously.
 
                         
                         References 
                          1. Chlorine Scrubbing System, Chlorine Institute, Inc. 
                          2. Chlorine Handbook, George White 
                          3. RJ Technical Manual 
                             |