Daeil Aqua Co., Ltd. ---- Manufacturer of Industrial & HVAC Cooling Towers

Professional Engineeing Publication < HOME 

Professional Engineeing Publication

 

 

 

 


 

 

 

 

 

1) Design Factors

All coupling types and designs are subjected to common design criteria.

(1) Transmit Torque: Torque is transmitted from the shaft to the hub via key and keyway. The following specifications should be included:

   * AGMA Class I Clearance fit bores (reference AGMA 9002-A86)
   * Standard width and depth keyways (commercial fit key - reference AGMA 9002-A86)
   * One self-locking set screw over the key. A second set screw at 90* can be provided for more
      positive retention.
   * Minimum let length should fill the entire hub keyway.
   * A 2.0 minimum service factor based on motor nameplate horsepower. Coupling must be rated
      for peak torque produced by motor.

(2) Misalignment: The ability to accept misalignment is another prime function of couplings. Shafts become misaligned as a result of many natural and unavoidable causes. Heat, vibration, bearing wear, the setting of foundations, etc. all tend to alter initial alignment. In general, coupling life is increased when shafts are initially aligned very carefully.

   * Aligned shafts. When two shafts are coaxial.
   * Parallel offset misalignment. When two shafts are not coaxial but their axes are not parallel.
   * Angular misalignment. When two shafts are not coaxial but their axes are not parallel.

a. symmetrical angular misalignment. When the axes of the two shafts intersect midway between the shaft ends.

b. Non symmetrical angular misalignment. When the axes of two shafts intersect, other than midway between the shaft ends.


   * Axial misalignment. Where the shafts are parallel but move in and out relative to each other.

(3) Corrosion Resistant: Corrosion resistance is a criterion which must consider the specific cooling tower conditions encountered. The life of a coupling will be affected by a corrosive chemical attack of its components. Many forms of corrosion exist, and any one of them can be detrimental to the life of a coupling or other components.

(4) Resonant Frequency: The first lateral critical speed of a cooling tower coupling and drive shaft assembly should b greater than 1.3 times the maximum operating speed. Higher safety factors may be applied to longer shafts. Addax is using two safety factors for (1.35 or 1.40) Composite Coupling Shafts and you can choose one of them. The past experience with Addax Composite Shafts is that the 1.4 safety margin is conservative and there is no problem with using 1.35 safety margin. The first critical RPM of a simply supported coupling and drive shaft assembly is approximately obtained from:

Critical Speed = (K/L2) x (OD2 + ID2)0.5

Where, K = 3.0 x 106 to 10.0 x 106 depending on coupling flexibility
           L= DBSE OD & ID = outside & inside diameter shaft spacer tube

(5) Forcing Frequency: The term of "Forcing Frequency" is used to describe a vibration pulse that may be excited a response from an element of another system during operation. Forcing frequencies are; blade pass frequency, acceleration/ deceleration pulses from couplings, impulses from reciprocating engines or motors and gear mesh frequencies. These are all examples of the generic term of "forcing frequency". Forcing frequencies of concern in cooling towers are blade pass and gear mesh frequencies.

There are three natural critical frequencies of concern,

a. Axial Natural Frequency (ANF) relates to the axial stiffness of composite tube and spring rate of flexible element;

b. Torsional Natural Frequency (TNF) relates to the torsional stiffness of the composite tube, the spring rate of the connected shafts of motor & gear reducer, and the rotational inertia of the motor and gear reducer and drive shaft; 

c. Lateral Natural Frequency (LNF) relates to the beam stiffness of the composite tube and the way it is connected to the shafts of motor and gear reducer.

ANF is not usually a problem in cooling tower applications because of the axial stiffness of the flexible element and because the shafts of motor and gear reducer do not float back and forth along their axis. ANF is a consideration on sleeve bearing motors or turbines where they are allowed to seek a magnetic center or operating equilibrium. An ANF condition will cause the drive shaft to oscillate (vibrate) back and forth parallel to the axis of rotation. This condition would destroy the flexible elements very quickly.

TNF is not usually a problem on cooling tower applications due to the relatively large WR2 (rotational inertia) of the fan and gear reducer compared to the composite shaft. The mass of the coupling is very small compared to the fan-gear reducer combination and motor. Also, the load is very constant. There is no pulse from the driver or driven equipment as with a reciprocating engine to excite the drive shaft torsionally. In general, there are no forcing frequencies present in cooling tower applications to create a harmonic condition with the ANF or TNF of the drive shaft.

LNF or lateral critical speed of the drive shaft can be excited by a gear mesh frequency or fan blade passing frequency. Coincidence with a gear mesh frequency is rare. When it does occur, it usually occurs during start-up when the gear reducer is accelerating to operating speed. The duration is very short, usually less than 2 or 3 seconds. The gear mesh frequency could be understood as a problem of composite shaft (chatter noise or rattle noise) when a series of vibration readings were not taken. Because the shaft could be amplifying the chatter noise coming from the gear reducer.

A more common problem with Lateral Critical Speed (Nlc) of the composites drive shaft has been with Blade Passing Frequency (BPF) coinciding with an integer fraction thereof (1/1. 1/2, 1/3...), or stated as Nlc being equal to 1, 2, or 3 times BPF. Integer increments greater than 3 times do not present a problem because there is not usually enough energy in the vibrations to cause a significant response.

A algorithm to avoid effectively harmonic responses in the cooling tower fans is as follows:

   * Select the proper flexible element for the required power rating. The motor breakdown torque
      must be less than the peak torque rating of the flexible element series. Apply required service
      factor (minimum 2.0) to continuous torque load.

   * Nlc of the composite drive shaft must be greater than 1.35 times the operating speed. This means
      that Nlcwill be approximately 2,430 CPM (1.35 x 1,800 for 60 hz & 4 poles motor) or 2,025
      CPM (1.35 x 1,500 for 50 hz & 4 poles motor). If the application is variable speed, we
      recommend to apply of 2.1 times the maximum operating speed. These are general rules and not
      firmly fixed.

      If all parameters are known, BPF, Nlc from actual tests, and operating RPM range, then
      deviation from the 1.35 safety factor may be acceptable. Please refer to the attached critical
      speed curve.

   * Once an initial selection is made on the basis of above, then the actual Nlc of the drive shaft
      model selected is compared to 1, 2, and 3 times the BPF. If any of these increments fall in the
      range of + 5% to - 10% of the Nlc, then the selection is rejected and the next procedures are as
      follows:

      - Extend or shorten the length of shaft.
      - Change the model of shaft until a solution is derived.

   * If there is a sufficient quantity of identical drive shafts for an application (20 or more), then maker
      can design a special composite tube and manufacture it specifically for the application criteria.
      The filament winding allows the ability to tune the Nlc into a range out of concern. Please contact
      us with applications like this for a possible alternative to a standard model.

During the operation of cooling tower the shaft would have been broken due to the resonant frequency margin between blade passing frequency and critical frequency of shaft. That is, the shaft would be broken because of the rapid decrease of dynamic stiffness of shaft due to close operation to the critical speed of shaft.

The fan blade passing frequency which is obtained from a formula of BPF = No. of Blades x Fan rpm (CPM) is effecting to the shaft as the forcing frequency and is being acted as the natural frequency against the shaft itself. Accordingly, the frequency of shaft itself will be harmonic with the natural frequency due to the fan revolution. If the natural frequency occurs within the range of -10% to +5% of critical speed, the amplitude of vibration will be dramatically increased, will reduce the stiffness of shaft, and ultimately the shaft could be broken.

The most often occurrence of a Nlc problem has been at 3 times BPF in the selection process. This is due to the initial criteria of the 1.35 safety factor times the operating speed of motor. Applying a 1.35 safety factor on the operating RPM usually places the Nlc out of the range of 1 or 2 times the BPF. We believe the phenomenon of 1, 2, or 3 times BPF exciting the Nlc of the composite drive shaft is due the pressure pulse created by the cooling tower fan blade passing over the drive shaft. This pressure pulse forces the drive shaft to deflect which causes the drive shaft to bounce up and down. When the pressure pulse is equal to 1/2, 1/2, or 1/3 the Nlc of the drive shaft it induces a harmonic response and the drive shaft vibrates continuously at its critical frequency.



Prior to the introduction of composite drive shaft for cooling towers, 3 times BPF as a possible harmonic problem was not considered first. The metal drive shafts may not have responded to this harmonic condition for at least two reasons; the steel drive shaft did not span the same length in a single section so their Nlc may have been out of the range; and/or the larger mass and weight of the steel drive shafts made them less susceptible to the pressure pulse from the fan blade passing overhead.



To the below curve is a typical one of a composite cylinder versus RPM. The peak amplitude is the Nlc of the shaft. The studies indicate that a vibration amplitude of 5 mils or greater occurs within the range of +/- 7.5% of the peak amplitude.



There will be some variance in the calculated value of Nlc and the actual. The studies indicates that the actual Nlc varies by +/- 2% of the calculated value. This variance in the manufacturing process. There is also some evidence that suggests the Nlc as measured by bump test when installed in the cooling tower is somewhat lower than the calculated values. Currently the studies for this phenomenon in order to gain the ability to predict accurately what is happening are proceeded by maker.

The resonant frequency margin with blade passing frequency is obtained from below formulas per the value in difference of first, second, or mode blade passing frequency and critical speed of drive shaft;



(6) Dynamic Balance: Dynamically balanced spacers are necessary to keep the coupling induced vibration to a minimum. Dynamic balancing at operational speed is recommended because long spacers can be considered as flexible rotors. The dynamic balance classes specified by AGMA Standard 515 are recommended.


To be continued. Please press the next button....