1) General
The scrubbing system design
must follow good engineering practice and adhere to
state and local regulations and company policy. Permitting
is generally required. Specific performance criteria
are beyond the scope of this pamphlet. Sections 2) through
5) contain process design considerations specific to
chlorine that can aid design engineers in developing
a chlorine scrubbing system.
2) Capacity Decision
The scrubbing system capacity
decision cannot be made until the stream to be scrubbed
is defined. The composition must be predicted fairly
accurately. A stream containing a high concentration
of chlorine can be neutralized readily using a large
volume of caustic in a relatively small contact area
system. When the stream to be scrubbed contains more
than 20 to 30% by volume inert, care must be taken to
assure adequate contact in order to remove the last
traces of chlorine from the gas stream.
Generally, caustic at 20%
or less concentration is used for scrubbing purposes.
The freezing temperature of a 20% solution is -16.6oF
(-27oC). Also, when a 20% solution of
caustic is reacted with chlorine a nearly saturated
salt solution is formed. Scrubbing with higher caustic
concentrations will result in higher peak reaction temperatures
and crystal salt precipitation with attendant pluggage
potential. It must be realized that if a batch scrubber
is designed properly, the starting solution can exceed
20% by weight, if the solution is not chlorinated to
the end point. Each application will need careful review
to ensure salt precipitation can not occur.
Potentially reactive or hazardous
components must be defined and considered in the scrubbing
system design. For example, in chlorine producing plants,
it is sometimes necessary to neutralize a stream made
up of chlorine, air, and hydrogen. When the chlorine
in this stream is neutralized, the hydrogen concentration
may increase through the reactive/explosive ranges.
(See Pamphlet MIR-121, ref. 6.1). Special attention
must be paid to potentially reactive or explosive components
during the process design.
The fluid state of chlorine,
gas or liquid must be considered during the design process.
If liquid chlorine is fed to a system designed to process
gas, a violent and uncontrolled reaction will result.
This can lead to a chlorine release.
In a batch reaction system,
the duration and concentration of the vent stream flow
must be known to size the process equipment appropriately.
3) Reaction Temperatures
Table 6.1 shows the overall
heat load on a chlorine scrubber that is reacting chlorine
at an instantaneous rate equivalent to 100 tons (90.7
metric tons) per day. On a hourly basis this is equivalent
to 8,333 lbs/hr (3,720 kg/hr). The "no decomposition
" line assumes that all chlorine reacts to sodium
hypochlorite. The "decomposition" line assumes
that 25% of the sodium hypochlorite produced decomposes
to oxygen and salt.
Caution!
The assumed 25% decomposition
is noted for illustrative purposes only. The amount
of decomposition will be in influenced by the reaction
temperature and the presence of impurities which can
catalyze the decomposition reaction. The expected decomposition
must be developed for each individual system. In the
absence of external cooling and in the absence of information
on the specific catalysts present, then a conservative
estimate of the temperature rise is determined by assuming
75% decomposition.
Table 6.1 |
DRY CHLORINE FEED |
No
Decomposition |
5.2
x 106 BTU/hr |
(1.31
x 10 Kcal/hr) |
Decomposition |
6.9
x 10 6 BTU/hr |
(2.02
x 10 Kcal/hr) |
(saturated at 190oF) |
No
Decomposition |
7.8
x 106 BTU/hr |
(1.97
x 10 K-cal/hr) |
Decomposition |
8.5
x 106 BTU/hr |
(2.15
x 10 K-cal/hr) |
When neutralizing water saturated
chlorine with stoichiometric quantities of 15 to 20%
caustic, the heat generated can bring the solution to
the boiling temperature. The water vapor generated by
the boiling solution dilutes the chlorine and reduces
the mass transfer efficiency of the scrubber. Thus,
it is desirable to maintain the solution temperature
well below the boiling temperature. The transfer of
heat from the solution to an external cooling system
can be the obvious choice if capacity is available.
If external cooling is not available, temperature control
can also be accomplished by reducing the initial caustic
concentration or scrubbing with excesses of caustic.
Graphs 6.3A and 6.3B show the effect on scrubber liquor
temperature rise when initial caustic strength varies
from 5 to 20% and when one to four times the stoichiometric
quantity of caustic is used for neutralization. Note
that the following graphs illustrate chlorine saturated
with water vapor. Dry chlorine scrubbers have lower
heat loads which can be derived from the data in Table6.1.
Graphs 6.3A and 6.3B illustrate
the heat effects of the reaction. Temperature increases
are approximates. A rigorous thermal analysis is required
for each scrubber design to ensure proper materials
of construction are employed.
4) Caustic Soda Scrubbing
Solution
When caustic soda is used
as a scrubbing solution, these guidelines should be
considered.
- In order to maintain scrubber
capacity to react chlorine, there must always be some
excess of caustic. In emergency scrubber applications
where flows and concentrations cannot be guaranteed,
sufficient excess caustic should be made available.
For in-process scrubbers where flows are known only
minimal excess caustic is necessary.
- In many applications,
it is desirable and technically feasible to deplete
the scrubbing liquor to as low as 10 grams per liter
of NaOH. When low concentrations of caustic are used,
several items should be considered. As pH drop below
10, conditions become favorable for the formation
of sodium chlorate. Under basic conditions sodium
chlorate is quite stable and will contaminate the
effluent stream.
- Total depletion of caustic
is to be avoided. Accidental depletion will negate
the reaction process and chlorine gas will be evolved.
The resulting acidic conditions will cause sodium
hypochlorite to decompose to salt and oxygen. The
oxygen evolution can be violent.
- Batch scrubbing operations
using ejector venturi devices or packed columns shall
have sufficient caustic soda solution flowing to always
exceed the 1.128 caustic to chlorine ratio. At the
end of the batch scrubbing cycle when the caustic
concentration has been reduced to low levels, care
must be taken to assure adequate mass transfer.
- When strong caustic solutions
are chlorinated to the end point, the salt concentration
can be high enough to become saturated in the resulting
solution and it can precipitate from the solution.
System pluggage is a hazard. Precipitation will occur
if the beginning solution is greater than approximately
22% by weight. The salt precipitation is also temperature
dependent.
- Although caustic soda
dissolves in water to form various concentrations,
care must be taken of the temperature at which the
solutions separate solid hydrates. These "freezing
curves" are available in literature published
by producers and typical values are as follows:
5% @ 25oF
(-3.9oC) |
10% @ 18oF
(-7.8oC) |
15% @ 4oF
(-15.6oC) |
18% @ -11oF
(-23.8oC) |
20% @ -16.6oF
(-27oC) |
25% @ 0oF(-17.8oC) |
19.09% caustic has the lowest freezing temperature
of any concentration of caustic. The freezing point
of this solution is -18.4oF (-28oC).
50% caustic soda, the common commercially available
strength, freezes at 54oF (12.2oC)
5) Specific Safety Considerations
The following areas are critical
when the initial design decisions are made:
- Adequate instrumentation
should be provided for monitoring, analyzing, recording,
and controlling the critical operating parameters.
- The fluid state of the
chlorine should be consistent with the process design
criteria. The process should be designed to prevent
liquid chlorine from entering a scrubber designed
for gas.
- If the possibility of
explosive gas mixtures exists, steps should be taken
to prevent same, e.g. provisions for dilution with
air.
- Installation of a system
to prevent hypochlorite of caustic solutions from
flowing back into the chlorine lines and corroding
piping and valves, such as a barometric loop.
- Caustic and water when
mixed will have less volume than the sum of the two
streams. However, the resultant solution when chlorinated
to low excess caustic levels will expand. This expansion
at high solution strengths of beginning caustic can
result in an approximate 10% increase in volume more
than the total sum of caustic and water volume. Always
design the scrubbing system for the theoretical maximum
volume.
- Batch scrubber system,
when used for room scrubbing or many types do process
scrubbing, will cause the caustic to react with any
CO2, present to produce sodium carbonate.
Each application must be reviewed to ensure the caustic
depletion and carbonate/bicarbonate precipitation
during operation are not problems.
- Materials of construction
should be consistent with the process under both design
and upset conditions, e.g. if titanium, which is excellent
in wet chlorine, is allowed to contact dry chlorine,
spontaneous combustion will result.
|